TMR-DA-02... Type TMR Current Sensor
Category:
Product information: TFY-TMR-Z80-003(铭牌型号:TMR-DA-02...型TMR电流传感器产品规格书A1.1_20260727(2).pdf
Product Description
Scope of Application
This specification applies to Class B three-phase electric energy meters with direct connection.
Applicable Conditions
Atmospheric pressure: 63 kPa to 106 kPa, at altitudes below 4,000 m.
Climate and environmental conditions: No gases, vapors, chemical deposits, dust, or other corrosive or explosive substances that would adversely affect the insulation of the instrument transformer.
Ambient temperature and humidity are shown in Table 1.
Table 1: Ambient Temperature and Humidity Ranges
| Conditions | Scope | Conditions | Scope |
| The specified operating temperature | -40℃~70℃ | Annual average humidity | ≤75% |
| Maximum operating temperature | -40℃~85℃ | 30 days (these days are naturally distributed throughout the year) | ≤95% |
| Storage temperature | -40℃~85℃ | It occasionally appears on other days. | ≤85% |
Reference Standard
JBT 10665-2016 “Miniature Current Transformers for Electric Energy Meters” JJG313-2010 “Verification Procedure for Measuring Current Transformers”
Q/GDW 11179.15-2023 “Technical Specification for Components Used in Electric Energy Meters – Part 15: Current Transformers” GBT 20840.8-2007 “Instrument Transformers – Part 8: Electronic Current Transformers”
Structural dimensions

Figure 1: Dimensional Drawing
Note: P1 and P2 are the primary current input terminals, and P1 and SCN-2P-1 are like-named terminals.
SCN-2P terminals: 1 (red) connects to the positive terminal of the current-sampling input, and 2 (black) connects to the negative terminal of the current-sampling input.
SCN-3P terminals: 3 (yellow) to VEE, 4 (black) to GND, and 5 (red) to VCC.
Electrical Requirements
Table 2 Electrical Characteristics
| Characteristics | Parameter | Project | Parameter |
| Primary fundamental current | 5A | Secondary fundamental current | 2 mA |
| Maximum current at the primary side | 80A | Secondary load | 10Ω |
| Accuracy requirements | See Table 3. | Same-name port | See Figure 1. |
The ratio error and phase error shall not exceed the values specified in Table 3 below.
Table 3 Limits for Ratio Error and Phase Error (at 23°C)
| Accuracy class | Ratio error ±% | Phase error ±’ | ||||||||||
| 0.01Ib | 0.05Ib | 0.2Ib | Ib | 1.2Ib | Imax | 0.01Ib | 0.05Ib | 0.2Ib | Ib | 1.2Ib | Imax | |
| 0.2S | 0.75 | 0.35 | 0.2 | 30 | 15 | 10 | ||||||
Note: The difference between the error values at each current test point shall not exceed 0.2S‑class values. When a half‑wave is applied within the range of Ib to 1.2Imax, the variation in ratio error shall be no greater than ±0.2%, and the variation in phase error shall be no greater than 15′.
The absolute value of the current ramp‑up/ramp‑down error shall not exceed the values specified in Table 4 below.
Table 4: Limits for Load Current Rise and Fall Variation
| Accuracy class | Ratio error variation ±% | Phase error variation |
| 0.2 | 0.1 | 10 |
Note: The current range is 0.05Ib to Imax.
Other requirements
| Serial number | Test conditions | Technical Requirements |
| 1 | Short-time overcurrent test Q/GDW 11179.15-2015 - 7.2.4 |
After testing, the change in ratio error is ≤ ±0.1%, and the change in phase error is ≤ 5’. |
| 2 | Temperature Rise Test Q/GDW 11179.15-2015 - 7.2.5 |
During the test, the enclosure temperature rise shall not exceed 25 K. |
| 3 | Power-frequency withstand voltage test Q/GDW 11179.15-2015 - 7.2.7 |
No destructive discharges were observed during the test. |
| 4 | Impulse Voltage Test Q/GDW 11179.15-2015 - 7.2.8 |
Following the test, no visible damage was observed, and the results comply with the error variation limits specified in Tables 3 and 4. |
| 5 | Insulation Resistance Test Q/GDW 11179.15-2015 - 7.2.9 |
The insulation resistance between the primary winding and the secondary winding shall not be less than 1000 MΩ (DC 500 V). |
| 6 | Mechanical Property Testing Q/GDW 11179.15-2015 - 7.3 |
There are no fractures at the secondary winding terminals. |
| 7 | High-temperature test Q/GDW 11179.15-2015 - 7.4.1 |
Following the test, no visible damage was observed, and the results comply with the error variation limits specified in Tables 3 and 4. |
| 8 | Low-temperature test Q/GDW 11179.15-2015 - 7.4.2 |
Following the test, no visible damage was observed, and the results comply with the error variation limits specified in Tables 3 and 4. |
| 9 | High-Temperature, High-Humidity Test Q/GDW 11179.15-2015 - 7.4.3 |
Following the test, no visible damage was observed, and the results comply with the error variation limits specified in Tables 3 and 4. |
| 10 | Temperature Shock Test Q/GDW 11179.15-2015 - 7.4.4 |
Following the test, no visible damage was observed, and the results comply with the error variation limits specified in Tables 3 and 4. |
Key words:
Related Products
Welcome your message consultation
Any questions? Keep in touch. We 'd love to hear from you.